SIMATIC S7-400, POWERSUPPLY PS 405: 20A, WIDE RANGE, 24/48/60V DC, 5V DC/20A, ATEXAPPROBATIONIDENTIFICATION |
|
Supply voltage |
Rated value, 24 V DC |
Yes |
Rated value, 48 V DC |
Yes |
Rated value, 60 V DC |
Yes |
permissible range, lower limit (DC) |
19.2 V; Dynamic 18.5 V |
permissible range, upper limit (DC) |
72 V; dynamic 75.5 V |
Mains buffering |
Mains/voltage failure stored energy time |
20 ms |
Mains buffering according to NAMUR recommendation |
Yes |
Input current |
Rated value at 24 V DC |
7 A |
Rated value at 48 V DC |
3.2 A |
Rated value at 60 V DC |
2.5 A |
Inrush current, max. |
56 A; Full width at half maximum 1.5 ms |
Output voltage |
Rated value, 5 V DC |
Yes |
Rated value, 24 V DC |
Yes |
Output current |
for backplane bus (5 V DC), max. |
20 A; no base load required |
for backplane bus (24 V DC), max. |
1 A; idling-proof |
Short-circuit protection |
Yes |
Power |
Power consumption, typ. |
168 W |
Power loss |
Power loss, typ. |
44 W |
Battery |
Backup battery |
Backup battery |
|
Backup battery (optional) |
Yes; 2 x lithium AA; 3.6 V/2.3 Ah |
Hardware configuration |
Slots |
required slots |
2 |
Galvanic isolation |
primary/secondary |
Yes |
Degree and class of protection |
Protection class |
1; with protective conductor |
Standards, approvals, certificates |
FM approval |
Yes; Ta: 0 °C to 60 °C T4 |
Dimensions |
Width |
50 mm |
Height |
290 mm |
Depth |
217 mm |
Weights |
Weight, approx. |
1300 g |
Status |
Jul 9, 2014 |