![](/storage/image/d/image/data/SIEMENS_Original/6ES7/138/6ES7138-4FB02-0AB0/6ES71384FB020AB0.jpg) |
SIMATIC DP, ELECTRON. MODULE F. ET200S, 4 F-DO PROFISAFE, DC 24V/2A, 30 MM WIDTH UP TO CATEGORY 4 (EN954-1) ALSO USEABLE IN PROFINET- NETWORKS WITH IM151-3 HF |
Supply voltage |
Load voltage L |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
No |
Input current |
from load voltage L (without load), max. |
typ. 100 mA |
from backplane bus 3.3 V DC, max. |
28 mA |
Power loss |
Power loss, typ. |
3.5 W |
Digital outputs |
Number of digital outputs |
4 |
Limitation of inductive shutdown voltage to |
typ. (L ) -47 V |
Controlling a digital input |
No |
Switching capacity of the outputs |
● Lamp load, max. |
10 W |
Load resistance range |
● lower limit |
12 Ω |
● upper limit |
1 kΩ |
Output voltage |
● for signal "1", min. |
L (-2,0 V), current sourcing switch: L (-1,5 V), voltage drop on current sinking switch: max. 0.5 V |
Output current |
● for signal "1" rated value |
2 A |
● for signal "1" permissible range for 0 to 60 °C, min. |
20 mA |
● for signal "1" permissible range for 0 to 60 °C, max. |
2.4 A |
● for signal "0" residual current, max. |
0.5 mA; Current-sourcing: max. 0.5 mA; Current sinking: max. 4 mA |
Parallel switching of 2 outputs |
● for uprating |
No |
● for redundant control of a load |
No |
Switching frequency |
● with resistive load, max. |
30 Hz |
● with inductive load, max. |
0.1 Hz |
● on lamp load, max. |
10 Hz |
Total current of the outputs (per group) |
all mounting positions |
— up to 60 °C, max. |
4 A |
horizontal installation |
— up to 40 °C, max. |
6 A |
— up to 55 °C, max. |
5 A |
vertical installation |
— up to 40 °C, max. |
4 A |
Cable length |
● Cable length, shielded, max. |
200 m |
● Cable length unshielded, max. |
200 m |
Interrupts/diagnostics/status information |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Wire-break |
Yes |
● Short-circuit |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
● Status indicator digital output (green) |
Yes |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
● between the channels and the load voltage L |
No |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
● acc. to EN 954 |
Cat. 4 |
● acc. to IEC 61508 |
SIL 3 |
Dimensions |
Width |
30 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
85 g |
last modified: |
21.08.2014 |