SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; /- 10V, 11 BIT, 12 MBIT/S |
Supply voltage |
permissible range, lower limit (DC) |
18.5 V |
permissible range, upper limit (DC) |
30.2 V |
Load voltage 1L |
● Rated value (DC) |
24 V; Value at t < 0.5 s: 35 V |
Input current |
from supply voltage L , max. |
200 mA; Logic |
Power losses |
Power loss, typ. |
2.4 W |
Hardware configuration |
Rack |
● Required terminal block |
TB8 |
Analog outputs |
Number of analog outputs |
4 |
Voltage output, short-circuit protection |
Yes; Electronic; max. 1 output in parallel |
Voltage output, short-circuit current, max. |
25 mA |
Current output, no-load voltage, max. |
18 V |
Output ranges, voltage |
● 0 to 10 V |
Yes |
● -10 to 10 V |
Yes |
Output ranges, current |
● 0 to 20 mA |
Yes |
● 4 to 20 mA |
Yes |
Connection of actuators |
● for voltage output two-wire connection |
Yes |
● for voltage output four-wire connection |
Yes |
● for current output two-wire connection |
Yes |
Load impedance (in rated range of output) |
● with current outputs, max. |
300 Ω |
● with current outputs, inductive load, max. |
1 mH |
Cable length |
● Cable length, shielded, max. |
100 m |
Analog value creation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
11 bit; Two''s complement |
● Conversion time (per channel) |
1 ms |
Settling time |
● for resistive load |
0.1 ms |
● for capacitive load |
3.3 ms |
● for inductive load |
0.5 ms |
Errors/accuracies |
Output ripple (based on output area, bandwidth 0 to 50 kHz), ( /-) |
0.05 % |
Linearity error (relative to output range), ( /-) |
0.05 % |
Temperature error (relative to output range), ( /-) |
0.02 %/K |
Crosstalk between the outputs, min. |
40 dB |
Repeat accuracy in steady state at 25 °C (relative to output area), ( /-) |
0.05 % |
Operational limit in overall temperature range |
● Voltage, relative to output area, ( /-) |
0.05 % |
● Current, relative to output area, ( /-) |
1 % |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to output area, ( /-) |
0.2 % |
● Current, relative to output area, ( /-) |
0.3 % |
Interfaces |
PROFIBUS DP |
● Transmission rate, max. |
12 Mbit/s |
Communication functions |
Bus protocol/transmission protocol |
PROFIBUS DP |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes; Parameterizable |
Diagnostics indication LED |
● Bus fault BF (red) |
Yes |
● Run mode RUN (green) |
Yes |
Galvanic isolation |
between electronic block and PROFIBUS DP |
Yes |
Galvanic isolation analog outputs |
● Galvanic isolation analog outputs |
No |
Degree and class of protection |
IP20 |
Yes |
Ambient conditions |
Operating temperature |
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
60 °C; 40°C for other mountings |
Air pressure |
● permissible range, min. |
795 hPa |
● permissible range, max. |
1 080 hPa |
Relative humidity |
● Operation, min. |
15 % |
● Operation, max. |
95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
● Operation, checked according to IEC 60068-2-6 |
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
● checked according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Connection method |
Inputs/outputs |
Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Dimensions |
Width |
160 mm; EB and TB |
Height |
130 mm; EB and TB |
Depth |
60 mm; EB and TB |
Weights |
Weight, approx. |
550 g; EB and TB |
last modified: |
08.09.2014 |