SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI HART, 2DMU, FOR CONNECTION OF HART 2-WIRE TRANSDUCER |
Input current |
from supply voltage L , max. |
320 mA |
Output voltage |
Power supply to the transmitters |
● short-circuit proof |
Yes |
● Supply current, max. |
23 mA; per channel |
Power loss |
Power loss, typ. |
2.7 W |
Analog inputs |
Number of analog inputs |
4 |
permissible input current for current input (destruction limit), max. |
90 mA |
Cycle time (all channels) max. |
120 ms; 30 ms basic conversion time x 4 channels with 60 Hz, 50 Hz interference frequency suppression |
Technical unit for temperature measurement adjustable |
Yes |
Input ranges |
● Voltage |
No |
● Current |
Yes |
● Thermocouple |
No |
● Resistance thermometer |
No |
● Resistance |
No |
Input ranges (rated values), currents |
● 4 to 20 mA |
Yes |
Cable length |
● Cable length, shielded, max. |
500 m |
Analog value generation |
Measurement principle |
integrating (Sigma-Delta) |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
13 bit |
● Integration time, parameterizable |
No |
● Interference voltage suppression for interference frequency f1 in Hz |
50 / 60 Hz |
Smoothing of measured values |
● parameterizable |
Yes; in 4 stages |
● Step: None |
Yes; 1 x cycle time |
● Step: Low |
Yes; 4 x cycle time |
● Step: Medium |
Yes; 32 x cycle time |
● Step: High |
Yes; 64 x cycle time |
Encoder |
Connection of signal encoders |
● for current measurement as 2-wire transducer |
Yes |
— Burden of 2-wire transmitter, max. |
750 Ω |
Errors/accuracies |
Linearity error (relative to input range), ( /-) |
0.015 % |
Temperature error (relative to input range), ( /-) |
0.005 %/K |
Crosstalk between the inputs, min. |
-50 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), ( /-) |
0.01 % |
Operational error limit in overall temperature range |
● Current, relative to input area, ( /-) |
0.15 % |
Basic error limit (operational limit at 25 °C) |
● Current, relative to input area, ( /-) |
0.1 % |
Interference voltage suppression for f = n x (f1 /- 1 %), f1 = interference frequency |
● Series mode interference (peak value of interference < rated value of input range), min. |
70 dB |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes; Parameterizable |
● Limit value alarm |
Yes; Parameterizable |
Diagnostic messages |
● Diagnostic information readable |
Yes |
● Wire-break |
Yes |
● Short-circuit |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
Standards, approvals, certificates |
CE mark |
Yes |
Highest safety class achievable in safety mode |
● acc. to IEC 61508 |
none |
● Performance level according to EN ISO 13849-1:2008 |
none |
Use in hazardous areas |
● Type of protection acc. to EN 50020 (CENELEC) |
II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I |
● Type of protection acc. to KEMA |
04 ATEX 1244 |
Dimensions |
Width |
30 mm |
Height |
129 mm |
Depth |
136.5 mm |
Weights |
Weight, approx. |
230 g |
last modified: |
21.08.2014 |