SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI, RTD, FOR CONNECTION OF RESISTANCE THERMOMETER PT100/NI100 |
|
Input current |
from supply voltage L , max. |
22 mA |
Power losses |
Power loss, typ. |
0.4 W |
Analog inputs |
Number of analog inputs |
4 |
Cycle time (all channels) max. |
320 ms; 66 ms basic conversion time x 4 channels with 60 Hz interference frequency suppression; 80 ms basic conversion time x 4 channels with 50 Hz interference frequency suppression |
Technical unit for temperature measurement adjustable |
Yes |
Input ranges |
Voltage |
No |
Current |
No |
Thermocouple |
No |
Resistance thermometer |
Yes |
Resistance |
Yes |
Input ranges (rated values), resistance thermometers |
Ni 100 |
Yes |
Input resistance (Ni 100) |
2000 kΩ |
Pt 100 |
Yes |
Input resistance (Pt 100) |
2000 kΩ |
Input ranges (rated values), resistors |
0 to 600 ohms |
Yes; Also 1000 ohms |
Input resistance (0 to 600 ohms) |
1000 kΩ |
Resistance thermometer (RTD) |
Characteristic linearization |
for resistance thermometer |
Yes |
Characteristic linearization |
Parameterizable |
Yes |
Cable length |
Cable length, shielded, max. |
500 m |
Analog value creation |
Measurement principle |
integrating (Sigma-Delta) |
Integrations and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. |
16 bit |
Integration time, parameterizable |
Yes |
Basic conversion time, including integration time, ms |
80 ms at 50 Hz; 66 ms at 60 Hz |
additional conversion time for wire break monitoring |
5 |
Interference voltage suppression for interference frequency f1 in Hz |
50 / 60 Hz |
Smoothing of measured values |
Parameterizable |
Yes; in 4 stages |
Step: None |
Yes; 1 x cycle time |
Step: low |
Yes; 4 x cycle time |
Step: Medium |
Yes; 32 x cycle time |
Step: High |
Yes; 64 x cycle time |
Encoder |
Connection of signal encoders |
for resistance measurement with two-wire connection |
Yes |
for resistance measurement with three-wire connection |
Yes |
for resistance measurement with four-wire connection |
Yes |
Errors/accuracies |
Linearity error (relative to input range), ( /-) |
0.015 % |
Temperature error (relative to input range), ( /-) |
0.02 %/K |
Crosstalk between the inputs, min. |
-50 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), ( /-) |
0.01 % |
Operational limit in overall temperature range |
Resistance thermometer, relative to input area, ( /-) |
0.15 %; Applies to resistances standard /- 0.8K climatic /- 0.3K |
Basic error limit (operational limit at 25 °C) |
Resistance thermometer, relative to input area, ( /-) |
0.1 %; Applies to resistances standard /- 0.5 K climatic /- 0.2 K |
Interference voltage suppression for f = n x (f1 /- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. |
70 dB |
Common mode interference, min. |
90 dB |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm |
Yes |
Limit value alarm |
Yes |
Diagnostic messages |
Diagnostic information readable |
Yes |
Wire break |
Yes |
Short circuit |
Yes |
Group error |
Yes |
Diagnostics indication LED |
Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
between the channels |
No |
between the channels and the backplane bus |
Yes |
between the channels and the load voltage L |
Yes; Channels and power bus |
Standards, approvals, certificates |
CE mark |
Yes |
Highest safety class achievable in safety mode |
acc. to IEC 61508 |
none |
Performance level according to EN ISO 13849-1:2008 |
none |
Use in hazardous areas |
Type of protection acc. to EN 50020 (CENELEC) |
II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I |
Type of protection acc. to KEMA |
04 ATEX 1247 |
Dimensions |
Width |
30 mm |
Height |
129 mm |
Depth |
136.5 mm |
Weights |
Weight, approx. |
230 g |
Status |
Jun 16, 2014 |