SIMATIC DP, ELECTRONIC MODULE 2 AO HIGH FEATURE I FOR ET 200S, 15 MM WIDE, /-20MA, 15 BIT SIGN, 4 .. 20MA, 15 BIT, OPERATIONAL LIMITS /-0.07% WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L |
● Rated value (DC) |
24 V; From power module |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L (without load), max. |
150 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Power losses |
Power loss, max. |
2 W |
Address area |
Address space per module |
● Address space per module, max. |
4 byte |
Analog outputs |
Number of analog outputs |
2 |
Current output, no-load voltage, max. |
18 V |
Cycle time (all channels) max. |
1.5 ms |
Output ranges, current |
● -20 to 20 mA |
Yes |
● 4 to 20 mA |
Yes |
Connection of actuators |
● for current output two-wire connection |
Yes |
● for current output four-wire connection |
No |
Load impedance (in rated range of output) |
● with current outputs, max. |
500 Ω |
● with current outputs, inductive load, max. |
1 mH |
Destruction limits against externally applied voltages and currents |
● Voltages at the outputs towards MANA |
15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20) |
● Current, max. |
50 mA; DC |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value creation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit; /-20 mA: 16 bits, 4 to 20 mA: 15 bits |
● Basic conversion time, ms |
1,0 |
Settling time |
● for resistive load |
0.25 ms |
● for capacitive load |
1 ms |
● for inductive load |
0.5 ms |
Errors/accuracies |
Output ripple (based on output area, bandwidth 0 to 50 kHz), ( /-) |
0.02 % |
Linearity error (relative to output range), ( /-) |
0.02 % |
Temperature error (relative to output range), ( /-) |
0.001 %/K |
Crosstalk between the outputs, min. |
60 dB |
Repeat accuracy in steady state at 25 °C (relative to output area), ( /-) |
0.01 % |
Operational limit in overall temperature range |
● Current, relative to output area, ( /-) |
0.07 %; for 250-ohm load impedance; /-0.3% for all other load impedances |
Basic error limit (operational limit at 25 °C) |
● Current, relative to output area, ( /-) |
0.03 %; for 250-ohm load impedance; /-0.26% for all other load impedances |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Substitute values connectable |
Yes; Parameterizable; 0 to 65535 (value range must be within rated range) |
Diagnostic messages |
● Diagnostic information readable |
Yes |
● Wire break |
Yes |
● Group error |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Parameter |
Remark |
7 byte |
Output type/range |
deactivated / /-20 mA / 4 to 20 mA |
Diagnosis: wire break |
Disable / enable |
Group diagnostics |
Disable / enable |
Behavior on CPU/Master STOP |
Output current and de-energized/substitute a value/keep last value |
Galvanic isolation |
Galvanic isolation analog outputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
● between the channels and the load voltage L |
Yes |
Permissible potential difference |
between MANA and M internally (UISO) |
75 VDC / 60 VAC |
Isolation |
Isolation checked with |
500 V DC |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
40 g |
last modified: |
25.09.2014 |