SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 16 DI/16 DO, 24V DC/0.5 A |
|
Supply voltage |
24 V DC |
Yes |
Reverse polarity protection |
Yes |
Hardware configuration |
Rack |
Required terminal block |
TB 32L |
Digital inputs |
Number of digital inputs |
16 |
Input voltage |
Type of input voltage |
DC |
Rated value, DC |
24 V |
for signal "0" |
-30 to 5 V |
for signal "1" |
13 to 30 V |
Input current |
for signal "1", typ. |
5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", min. |
2 ms |
at "0" to "1", max. |
4.5 ms |
Cable length |
Cable length for NAMUR input, shielded, max. |
1000 m |
Digital outputs |
Number of digital outputs |
16 |
Short-circuit protection |
Yes |
Output voltage |
Rated value (DC) |
24 V |
for signal "1", min. |
Ua - 3 V |
Output current |
for signal "1" permissible range for 0 to 60 °C, max. |
0.5 mA |
for signal "0" residual current, max. |
1 mA |
Switching frequency |
|
100 Hz |
|
0.5 Hz |
|
8 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
up to 60 °C, max. |
4 A |
Cable length |
|
1000 m |
Interfaces |
PROFIBUS DP |
Transmission rate, max. |
1.5 Mbit/s |
|
Yes |
Galvanic isolation |
between PROFIBUS DP and all other circuit components |
Yes |
Galvanic isolation digital inputs |
between the channels |
No |
between the channels and PROFIBUS DP |
Yes |
Degree and class of protection |
IP20 |
Yes |
Ambient conditions |
Operating temperature |
Ambient temperature / with horizontal mounting position / during operating phase / minimum |
0 °C |
Ambient temperature / with horizontal mounting position / during operating phase / maximum |
60 °C |
Air pressure |
Air pressure / minimum |
795 hPa |
Air pressure / maximum |
1080 hPa |
Relative humidity |
Relative humidity / during operating phase / minimum |
5 % |
max. relative humidity |
95 % |
Vibrations |
Operation, checked according to IEC 60068-2-6 |
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Connection method |
Inputs/outputs |
Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
Dimensions |
Width |
145 mm |
Height |
60 mm |
Depth |
60.5 mm |
Status |
May 9, 2014 |