SIMATIC DP, ELECTRONIC MODULE 2 AI HIGH FEATURE U FOR ET 200S, 15 MM WIDE, /-10V, 15 BI SIGN, /-5V,15BIT SIGN, 1..5V, 15BIT, OPERATIONAL LIMITS /-0.1% WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L |
● Rated value (DC) |
24 V; From power module |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L (without load), max. |
53 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Power losses |
Power loss, typ. |
0.85 W |
Address area |
Address space per module |
● Address space per module, max. |
4 byte |
Analog inputs |
Number of analog inputs |
2 |
permissible input voltage for voltage input (destruction limit), max. |
35 V; 35 V continuous; 75 V for max. 1 ms |
Cycle time (all channels) max. |
1 channel active per module: 75 / 90 / 30 ms; 2 channels active per module: 175 / 210 / 78 ms |
Input ranges |
● Voltage |
Yes |
Input ranges (rated values), voltages |
● 1 to 5 V |
Yes |
● -10 V to 10 V |
Yes |
● -5 V to 5 V |
Yes |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value creation |
Measurement principle |
integrating |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit; 1 to 5 V: 15 bits, /-10 V: 16 bits, /-5 V: 16 bits |
● Integration time, parameterizable |
Yes |
● Integration time, ms |
16,67 / 20 / 7,5 ms |
● Interference voltage suppression for interference frequency f1 in Hz |
60 / 50 Hz / no |
● Conversion time (per channel) |
1 channel active per module: 25 / 30 / 10 ms; 2 channels active per module: 58.3 / 70 / 26 ms |
Smoothing of measured values |
● Parameterizable |
Yes; In four stages by means of digital filtering |
● Step: None |
Yes; 1 x cycle time |
● Step: low |
Yes; 4 x cycle time |
● Step: Medium |
Yes; 32 x cycle time |
● Step: High |
Yes; 64 x cycle time |
Errors/accuracies |
Linearity error (relative to input range), ( /-) |
0.03 % |
Temperature error (relative to input range), ( /-) |
0.003 %/K; /- 0.003%: Calibration enabled; /- 0.015%: Calibration disabled |
Crosstalk between the inputs, min. |
-100 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), ( /-) |
0.01 % |
Operational limit in overall temperature range |
● Voltage, relative to input area, ( /-) |
0.1 %; /- 0,1 %: Calibration enabled; /0.5%; calibration disabled |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, ( /-) |
0.05 % |
Interference voltage suppression for f = n x (f1 /- 1 %), f1 = interference frequency |
● Series mode interference (peak value of interference < rated value of input range), min. |
90 dB |
● common mode voltage (USS < 2.5 V) , min. |
100 dB |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Diagnostic messages |
● Diagnostic functions |
Yes; can be read out (wire break diagnostics is not supported by this module.) |
● Group error |
Yes |
● Overflow/underflow |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Parameter |
Remark |
4 byte |
Diagnosis: wire break |
Disable / enable |
Measurement type/range |
deactivated / /-5 V / 1 to 5 V / /-10 V |
Interference frequency suppression |
Disable / enable |
Group diagnostics |
Disable / enable |
Overflow/underflow |
Disable / enable |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
● between the channels and the load voltage L |
Yes |
Permissible potential difference |
between the inputs (UCM) |
140V DC/100V AC |
Isolation |
Isolation checked with |
500 V DC |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
40 g |
last modified: |