SIMATIC DP, 1 ELECTRON. MODULE FOR ET 200S, 8 DO HIGH FEATURE DC24V/0,5A, 15 MM WIDTH, DIAGNOSIS SHORT CIRCUIT, SF-LED 1 PIECES PER PACKAGING UNIT |
Supply voltage |
Reverse voltage protection |
Yes; when using the same load voltage as on the power module |
Load voltage L |
● Rated value (DC) |
24 V; From power module |
● Reverse polarity protection |
Yes; polarity reversal can lead to the digital outputs being connected through |
Input current |
from load voltage L (without load), max. |
5 mA; Per channel |
from backplane bus 3.3 V DC, max. |
10 mA |
Address area |
Address space per module |
● with packing |
Not relevant |
● without packing |
1 byte |
Digital outputs |
Number of digital outputs |
8 |
Short-circuit protection |
Yes |
● Response threshold, typ. |
0.7 to 1.9 A |
Limitation of inductive shutdown voltage to |
L -(47 to 60 V) |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● Lamp load, max. |
5 W |
Load resistance range |
● lower limit |
48 Ω |
● upper limit |
3 400 Ω |
Output voltage |
● for signal "1", min. |
L (-1.0 V) |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range for 0 to 60 °C, min. |
7 mA |
● for signal "1" permissible range for 0 to 60 °C, max. |
600 mA |
● for signal "0" residual current, max. |
0.3 mA |
Output delay with resistive load |
● "0" to "1", max. |
300 µs |
● "1" to "0", max. |
600 µs |
Parallel switching of 2 outputs |
● for uprating |
No |
● for redundant control of a load |
Yes; per module |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
2 Hz |
● on lamp load, max. |
10 Hz |
Total current of the outputs (per group) |
horizontal installation |
— up to 60 °C, max. |
4 A |
vertical installation |
— up to 40 °C, max. |
4 A; At 55 °C and 24 V DC |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Isochronous mode |
Isochronous mode (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Short-circuit |
Yes; Module-wise |
Diagnostics indication LED |
● Group error SF (red) |
Yes; SF-LED (red) |
● Status indicator digital output (green) |
Yes; Per channel |
Parameter |
Remark |
1 byte |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation tested with |
500 V DC |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
40 g |
last modified: |
21.08.2014 |