SIMATIC DP, ELECTRON. MODULE ET200S: 2DO RELAY(FORM C CONT.) DC24V-48V/5A, AC24V-230V/5A, 15 MM WIDTH, FIRST-UP SIGNAL, WITH MANUAL ACTUATION |
|
Supply voltage |
Load voltage L |
Rated value (DC) |
24 V; From power module |
Reverse polarity protection |
Yes |
Input current |
from load voltage L (without load), max. |
30 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Power loss |
Power loss, typ. |
0.6 W |
Address area |
Address space per module |
with packing |
2 bit |
without packing |
1 byte |
Digital outputs |
Number of digital outputs |
2 |
Short-circuit protection |
No |
Limitation of inductive shutdown voltage to |
No |
Controlling a digital input |
Yes |
Output current |
for signal "1" rated value |
5 A |
for signal "1" minimum load current |
8 mA |
Switching frequency |
with resistive load, max. |
2 Hz |
with inductive load, max. |
0.5 Hz |
on lamp load, max. |
2 Hz |
Relay outputs |
Switching capacity of contacts |
Thermal continuous current, max. |
5 A |
Cable length |
Cable length, shielded, max. |
1000 m |
Cable length unshielded, max. |
600 m |
Isochronous mode |
Isochronous mode (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Substitute values connectable |
Yes; 0/1 |
Diagnostic messages |
Diagnostic functions |
No |
Diagnostics indication LED |
Status indicator digital output (green) |
Yes |
Parameter |
Behavior on CPU/master STOP, channel-wise |
Substitute a value/keep last value |
Galvanic isolation |
Galvanic isolation digital outputs |
between the channels |
Yes |
between the channels and the backplane bus |
Yes |
between the channels and the load voltage L |
Yes |
Isolation |
tested with |
Channels against backplane bus and load voltage L |
1500 V AC |
Load voltage L against backplane bus |
500 V DC |
Ambient conditions |
Extended ambient conditions |
relative to ambient temperature-atmospheric pressure-installation altitude |
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... 2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa ( 2000 m ... 3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa ( 3500 m ... 5000 m) |
Relative humidity |
with condensation, maximum |
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
50 g |
Status |
Jul 14, 2014 |