Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
18.5 V |
permissible range, upper limit (DC) |
30.2 V |
Input current |
Current consumption, max. |
130 mA |
I²t |
0.05 A²·s |
Power losses |
Power loss, typ. |
2 W |
Digital outputs |
Number of digital outputs |
8 |
short-circuit protection |
No |
Controlling a digital input |
Yes |
Output voltage |
● Rated value (DC) |
24 V |
Switching frequency |
● with resistive load, max. |
10 Hz |
● with inductive load, max. |
2 Hz |
Relay outputs |
Switching capacity of contacts |
— with inductive load, max. |
0.5 A |
— with resistive load, max. |
2 A |
— Thermal continuous current, max. |
5 A |
Cable length |
● Cable length unshielded, max. |
100 m |
Interfaces |
PROFIBUS DP |
● Transmission rate, max. |
12 Mbit/s |
● SYNC capability |
Yes |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
● Bus fault BF (red) |
Yes |
● Run mode RUN (green) |
Yes |
● Status indicator digital output (green) |
Yes |
Galvanic isolation |
between electronic block and PROFIBUS DP |
Yes |
Galvanic isolation digital outputs |
● Galvanic isolation digital outputs |
Yes |
● between the channels, in groups of |
1 |
Degree and class of protection |
Degree of protection to EN 60529 |
|
● IP20 |
Yes |
Ambient conditions |
Operating temperature |
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
60 °C |
Air pressure |
● permissible range, min. |
795 hPa |
● permissible range, max. |
1 080 hPa |
Relative humidity |
● Operation, min. |
15 % |
● Operation, max. |
95 % |
Vibrations |
● Operation, checked according to IEC 60068-2-6 |
Yes |
Shock test |
● checked according to IEC 60068-2-27 |
Yes |
Dimensions |
Width |
160 mm |
Height |
130 mm |
Depth |
60 mm |
Weights |
Weight, approx. |
650 g |
last modified: |
16.09.2014 |