![](/storage/image/d/image/data/SIEMENS_Original/6ES7/134/6ES7134-4FB51-0AB0/6ES71344FB510AB0.jpg) |
SIMATIC DP, ELECTRONIC MODULE ET 200S: 2 AI HIGH SPEED U, /-10V; 14 BIT, 15 MM WIDE, CYCLE TIME OF THE MODULE: 1MS, WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L |
● Rated value (DC) |
24 V; From power module |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L (without load), max. |
35 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Power loss |
Power loss, typ. |
0.8 W |
Address area |
Address space per module |
● Address space per module, max. |
4 byte |
Analog inputs |
Number of analog inputs |
2 |
permissible input voltage for voltage input (destruction limit), max. |
50 V; 50 V continuous; 100 V for max. 1 ms (mark to space ratio 1:20) |
Cycle time (all channels) max. |
1 ms; Per module |
Input ranges |
● Voltage |
Yes |
Input ranges (rated values), voltages |
● 1 to 5 V |
Yes |
● Input resistance (1 to 5 V) |
100 kΩ |
● -10 V to 10 V |
Yes |
● Input resistance (-10 V to 10 V) |
100 kΩ |
● -2.5 V to 2.5 V |
Yes |
● Input resistance (-2.5 V to 2.5 V) |
100 kΩ |
● -5 V to 5 V |
Yes |
● Input resistance (-5 V to 5 V) |
100 kΩ |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value generation |
Measurement principle |
Actual value encryption |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
14 bit; /-10 V: 13 bits sign, /-5 V: 13 bits sign, /-2.5 V: 13 bits sign; 1 to 5 V: 13 bits |
● Conversion time (per channel) |
0.1 ms |
Smoothing of measured values |
● parameterizable |
Yes; In four stages by means of digital filtering |
● Step: None |
Yes; 1 x cycle time |
● Step: Low |
Yes; 64 x cycle time |
● Step: Medium |
Yes; 128 x cycle time |
● Step: High |
Yes; 512x cycle time |
Encoder |
Connection of signal encoders |
● for voltage measurement |
Yes |
Errors/accuracies |
Linearity error (relative to input range), ( /-) |
0.01 % |
Temperature error (relative to input range), ( /-) |
0.01 %/K |
Crosstalk between the inputs, min. |
-50 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), ( /-) |
0.05 % |
Operational error limit in overall temperature range |
● Voltage, relative to input area, ( /-) |
0.3 % |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, ( /-) |
0.2 % |
Interference voltage suppression for f = n x (f1 /- 1 %), f1 = interference frequency |
● Common mode interference (USS < 2.5 V) , min. |
70 dB; Ucm < 100 Vpp |
Isochronous mode |
Isochronous mode (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Alarms |
● Hardware interrupt |
Yes; Parameterizable |
Diagnostic messages |
● Diagnostic information readable |
Yes |
● Wire-break |
No |
● Group error |
Yes |
● Overflow/underflow |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Parameter |
Remark |
12 byte |
Measurement type/range |
deactivated / /-10 V / /-5 V, /-2.5 V, to 5 V |
Group diagnostics |
Disable / enable |
Overflow/underflow |
Disable / enable |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
● between the channels and the load voltage L |
Yes |
Permissible potential difference |
between inputs and MANA (UCM) |
100 Vpp AC |
between MANA and M internally (UISO) |
75 VDC / 60 VAC |
Isolation |
Isolation tested with |
500 V DC |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
40 g |
last modified: |
21.08.2014 |