SIMATIC DP, 5 ELECTRON. MODULES ET200S: 2DO RELAY(FORM C CONT.) DC24V-48V/5A, AC24V-230V/5A, 15 MM WIDTH, FIRST-UP SIGNAL, 5 PIECES PER PACKAGING UNIT |
Supply voltage |
Load voltage L |
● Rated value (DC) |
24 V; From power module |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L (without load), max. |
30 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Power loss |
Power loss, typ. |
0.6 W |
Address area |
Address space per module |
● with packing |
2 bit |
● without packing |
1 byte |
Digital outputs |
Number of digital outputs |
2 |
Short-circuit protection |
No |
Limitation of inductive shutdown voltage to |
No |
Controlling a digital input |
Yes |
Output current |
● for signal "1" rated value |
5 A |
● for signal "1" minimum load current |
8 mA |
Parallel switching of 2 outputs |
● for uprating |
No |
● for redundant control of a load |
No |
Switching frequency |
● with resistive load, max. |
2 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
2 Hz |
Relay outputs |
Switching capacity of contacts |
— Thermal continuous current, max. |
5 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Isochronous mode |
Isochronous mode (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Substitute values connectable |
Yes; 0/1 |
Diagnostic messages |
● Diagnostic functions |
No |
Diagnostics indication LED |
● Status indicator digital output (green) |
Yes |
Parameter |
Remark |
3 byte |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels |
Yes |
● between the channels and the backplane bus |
Yes |
● between the channels and the load voltage L |
Yes |
Isolation |
tested with |
● Channels against backplane bus and load voltage L |
2500 V DC |
● Load voltage L against backplane bus |
500 V DC |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
50 g |
last modified: |
21.08.2014 |