General information |
Vendor identification (VendorID) |
0011h |
Supply voltage |
24 V DC |
Yes |
Reverse polarity protection |
Yes |
Mains buffering |
● Mains buffering, min. |
20 ms |
Load voltage 2L |
● Rated value (DC) |
24 V; 1L , 2L , 3L |
Input current |
from load voltage L1 (without load), max. |
100 mA; Per load group (L1 or L2 / L3 ) |
from supply voltage L , max. |
70 mA; L4 / L5 |
Power loss |
Power loss, typ. |
7 W |
Hardware configuration |
Rack |
● required terminal block |
TB 32L |
Digital outputs |
Number of digital outputs |
32 |
Short-circuit protection |
Yes |
● Response threshold, typ. |
0,7 A |
Limitation of inductive shutdown voltage to |
Typ. (L1 or L2 / L3 ) -55 V |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● Lamp load, max. |
5 W |
Load resistance range |
● lower limit |
41 Ω |
● upper limit |
28 000 Ω |
Output voltage |
● Rated value (DC) |
24 V |
● for signal "1", min. |
Ua - 3 V |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range for 0 to 60 °C, max. |
0.5 A |
● for signal "0" residual current, max. |
1 mA |
Output delay with resistive load |
● "0" to "1", max. |
50 ms |
● "1" to "0", max. |
200 ms |
Parallel switching of 2 outputs |
● for uprating |
No |
● for redundant control of a load |
Yes; only outputs of the same group |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
8 Hz |
Total current of the outputs (per group) |
all mounting positions |
— up to 60 °C, max. |
4 A |
horizontal installation |
— up to 40 °C, max. |
3 000 mA |
— up to 60 °C, max. |
2 000 mA |
all other mounting positions |
— up to 40 °C, max. |
2 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Interfaces |
PROFIBUS DP |
● Transmission rate, max. |
1.5 Mbit/s |
● SYNC capability |
Yes |
● Direct data exchange (slave-to-slave communication) |
Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
Communication functions |
Bus protocol/transmission protocol |
PROFIBUS DP |
Interrupts/diagnostics/status information |
Alarms |
● Alarms |
No |
Diagnostic messages |
● Diagnostic functions |
Yes |
Diagnostics indication LED |
● Bus fault BF (red) |
Yes |
● Status indicator digital output (green) |
Yes |
● Status indicator digital input (green) |
Yes |
● Monitoring 24 V voltage supply ON (green) |
Yes |
Galvanic isolation |
between PROFIBUS DP and all other circuit components |
Yes |
Galvanic isolation digital outputs |
● between the channels |
No |
● between the channels and PROFIBUS DP |
Yes |
Isolation |
Isolation tested with |
500 V DC |
Degree and class of protection |
IP20 |
Yes |
Ambient conditions |
Operating temperature |
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
60 °C; 40°C for other mountings |
Air pressure |
● permissible range, min. |
795 hPa |
● permissible range, max. |
1 080 hPa |
Relative humidity |
● Operation, min. |
5 % |
● Operation, max. |
95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
● Operation, tested according to IEC 60068-2-6 |
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
● tested according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Connection method |
Inputs/outputs |
Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
Dimensions |
Width |
145 mm |
Height |
60 mm |
Depth |
60.5 mm |
Weights |
Weight, approx. |
150 g |
last modified: |
21.08.2014 |