SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 32DO, 24V DC, 0.5A |
Supply voltage |
24 V DC |
Yes; L1 , L2 , L3 , L4 , L5 ; value at t < 0.5 s: 35 V |
permissible range, lower limit (DC) |
18.5 V |
permissible range, upper limit (DC) |
30.2 V |
Input current |
Current consumption, max. |
75 mA; From L5 ; logic |
I²t |
0.05 A²·s; with starting current inrush |
Power loss |
Power loss, typ. |
7.9 W |
Hardware configuration |
Rack |
● required terminal block |
TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC |
Digital outputs |
Number of digital outputs |
32 |
Short-circuit protection |
Yes; Electronic |
Limitation of inductive shutdown voltage to |
typ. (L1 to L4 ) -55 V |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● Lamp load, max. |
5 W |
Output voltage |
● Rated value (DC) |
24 V |
● for signal "0", max. |
2 V; idling |
● for signal "1", min. |
UE -3 V |
Output current |
● for signal "1" permissible range for 0 to 60 °C, min. |
0.5 A; in groups of 8 |
● for signal "0" residual current, max. |
1 mA |
Output delay with resistive load |
● "0" to "1", max. |
20 ms |
● "1" to "0", max. |
0.5 ms |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
8 Hz |
Total current of the outputs (per group) |
all mounting positions |
— up to 60 °C, max. |
2 A |
Cable length |
● Cable length unshielded, max. |
100 m |
Interfaces |
PROFIBUS DP |
● Transmission rate, max. |
12 Mbit/s |
● SYNC capability |
Yes |
Communication functions |
Bus protocol/transmission protocol |
PROFIBUS DP |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
● Bus fault BF (red) |
Yes |
● Run mode RUN (green) |
Yes |
● Status indicator digital output (green) |
Yes |
Galvanic isolation |
between electronic block and PROFIBUS DP |
Yes |
Galvanic isolation digital outputs |
● Galvanic isolation digital outputs |
Yes |
● between the channels, in groups of |
8 |
Degree and class of protection |
IP20 |
Yes |
Ambient conditions |
Operating temperature |
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
60 °C; 40°C for other mountings |
Air pressure |
● permissible range, min. |
795 hPa |
● permissible range, max. |
1 080 hPa |
Relative humidity |
● Operation, min. |
15 % |
● Operation, max. |
95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
● Operation, tested according to IEC 60068-2-6 |
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
● tested according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Connection method |
Inputs/outputs |
Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Dimensions |
Width |
235 mm; EB and TB |
Height |
130 mm; EB and TB |
Depth |
60 mm; EB and TB |
Weights |
Weight, approx. |
800 g; EB and TB |
last modified: |
31.07.2014 |