SIMATIC DP, 5 ELECTRON. MODULES ET 200S: 4DI UC 24V...48V, 15 MM WIDTH, WITH LED SF (GROUP FAULT), 5 PIECES PER PACKAGING UNIT |
|
Supply voltage |
24 V DC |
Yes; From power module |
permissible range, lower limit (DC) |
24 V |
permissible range, upper limit (DC) |
48 V |
24 V AC |
Yes |
permissible range, lower limit (AC) |
24 V |
permissible range, upper limit (AC) |
48 V |
Reverse polarity protection |
Yes; AC or DC automatic |
Input current |
from backplane bus 3.3 V DC, max. |
10 mA |
from supply voltage L , max. |
Dependent on encoder |
Encoder supply |
short-circuit protection |
Yes |
Output current |
Output current, rated value |
500 mA |
Output current, permissible range |
0 to 500 mA |
Power losses |
Power loss, typ. |
0.7 W |
Address area |
Address space per module |
with packing |
4 bit |
without packing |
1 byte |
Digital inputs |
Number of digital inputs |
4 |
Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Input voltage |
Type of input voltage |
AC/DC |
Rated value, UC |
24 V; 24 to 48 V UC |
for signal "0" |
-6 to 6 V DC, 0 to 5 V AC |
for signal "1" |
-15 to -57.6 V DC; -15 to 57.6 V DC; 15 to 48 V AC |
Frequency range |
47 bis 63 Hz |
Input current |
for signal "1", typ. |
10 mA; 4 to 10 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", max. |
15 ms |
at "1" to "0", max. |
15 ms |
Encoder connection |
Fixed current limitation for wire break monitoring, min. |
18 kΩ; Rated voltage 24 V (15 V to 35 V); rated voltage 48 V (30 V to 60 V): 39 kohms |
Cable length |
Cable length, shielded, max. |
1000 m |
Cable length unshielded, max. |
600 m |
Encoder |
Connectable encoders |
2-wire sensor |
Yes |
Permissible quiescent current (2-wire sensor), max. |
2 mA; (0.5 to 2 mA), a minimum load current is necessary for wire break diagnostics. |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Diagnostic messages |
Diagnostic functions |
Yes; Parameterizable |
Diagnostics indication LED |
Group error SF (red) |
Yes |
Status indicator digital input (green) |
Yes; per channel |
Galvanic isolation |
Galvanic isolation digital inputs |
between the channels |
No |
between the channels and the backplane bus |
Yes |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
35 g |
Status |
May 14, 2014 |