SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 32DO, 24V DC, 0.5A |
| Supply voltage |
| 24 V DC |
Yes; L1 , L2 , L3 , L4 , L5 ; value at t < 0.5 s: 35 V |
| permissible range, lower limit (DC) |
18.5 V |
| permissible range, upper limit (DC) |
30.2 V |
| Input current |
| Current consumption, max. |
75 mA; From L5 ; logic |
| I²t |
0.05 A²·s; with starting current inrush |
| Power loss |
| Power loss, typ. |
7.9 W |
| Hardware configuration |
| Rack |
| ● required terminal block |
TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC |
| Digital outputs |
| Number of digital outputs |
32 |
| Short-circuit protection |
Yes; Electronic |
| Limitation of inductive shutdown voltage to |
typ. (L1 to L4 ) -55 V |
| Controlling a digital input |
Yes |
| Switching capacity of the outputs |
| ● Lamp load, max. |
5 W |
| Output voltage |
| ● Rated value (DC) |
24 V |
| ● for signal "0", max. |
2 V; idling |
| ● for signal "1", min. |
UE -3 V |
| Output current |
| ● for signal "1" permissible range for 0 to 60 °C, min. |
0.5 A; in groups of 8 |
| ● for signal "0" residual current, max. |
1 mA |
| Output delay with resistive load |
| ● "0" to "1", max. |
20 ms |
| ● "1" to "0", max. |
0.5 ms |
| Switching frequency |
| ● with resistive load, max. |
100 Hz |
| ● with inductive load, max. |
0.5 Hz |
| ● on lamp load, max. |
8 Hz |
| Total current of the outputs (per group) |
| all mounting positions |
| — up to 60 °C, max. |
2 A |
| Cable length |
| ● Cable length unshielded, max. |
100 m |
| Interfaces |
| PROFIBUS DP |
| ● Transmission rate, max. |
12 Mbit/s |
| ● SYNC capability |
Yes |
| Communication functions |
| Bus protocol/transmission protocol |
PROFIBUS DP |
| Interrupts/diagnostics/status information |
| Diagnostics indication LED |
| ● Bus fault BF (red) |
Yes |
| ● Run mode RUN (green) |
Yes |
| ● Status indicator digital output (green) |
Yes |
| Galvanic isolation |
| between electronic block and PROFIBUS DP |
Yes |
| Galvanic isolation digital outputs |
| ● Galvanic isolation digital outputs |
Yes |
| ● between the channels, in groups of |
8 |
| Degree and class of protection |
| IP20 |
Yes |
| Ambient conditions |
| Operating temperature |
| ● horizontal installation, min. |
0 °C |
| ● horizontal installation, max. |
60 °C; 40°C for other mountings |
| Air pressure |
| ● permissible range, min. |
795 hPa |
| ● permissible range, max. |
1 080 hPa |
| Relative humidity |
| ● Operation, min. |
15 % |
| ● Operation, max. |
95 %; RH class 2 in accordance with IEC 1131-2 |
| Vibrations |
| ● Operation, tested according to IEC 60068-2-6 |
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
| Shock test |
| ● tested according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
| Connection method |
| Inputs/outputs |
Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
| Dimensions |
| Width |
235 mm; EB and TB |
| Height |
130 mm; EB and TB |
| Depth |
60 mm; EB and TB |
| Weights |
| Weight, approx. |
800 g; EB and TB |
| last modified: |
31.07.2014 |